10.26
SEL-311C Relay Instruction Manual Date Code 20060320
Serial Port Communications and Commands
Command Explanations
Below are sample SHOWSET commands for the SEL-311C model
0311C01x, showing all the factory default settings. The factory default
settings for the SEL-311C model 0311C00x are similar.
=>SHO <Enter>
Group 1
Group Settings:
RID =SEL-311C POTT TID =EXAMPLE: BUS B, BREAKER 3
CTR = 200
CTRP = 200 PTR = 2000.00 PTRS = 2000.00
Z1MAG = 7.80 Z1ANG = 84.00
Z0MAG = 24.80 Z0ANG = 81.50 LL = 100.00 APP = 311C
E21P = 3 E21MG = 3 E21XG = 3
E50P = 1 E50G = N E50Q = N
E51P = N E51G = Y E51Q = Y
E32 = AUTO EOOS = N ELOAD = Y ESOTF = Y
EVOLT = N E25 = N E81 = N EFLOC = Y
ELOP = Y ECOMM = POTT E79 = N EZ1EXT= N
ECCVT = N ESV = N ELAT = 16 EDP = 16
EDEM = THM EADVS = N
Z1P = 6.24 Z2P = 9.36 Z3P = 1.87
50PP1 = 0.50
Z1MG = 6.24 Z2MG = 9.36 Z3MG = 1.87
XG1 = 6.24 XG2 = 9.36 XG3 = 1.87
Press RETURN to continue
RG1 = 2.50 RG2 = 5.00 RG3 = 6.00
50L1 = 0.50
50GZ1 = 0.50
k0M1 = 0.726 k0A1 =-3.69
Z1PD = OFF Z2PD = 20.00 Z3PD = OFF
Z1GD = OFF Z2GD = 20.00 Z3GD = OFF
Z1D = OFF Z2D = OFF Z3D = OFF
50P1P = 11.25
67P1D = 0.00
51GP = 0.75 51GC = U3 51GTD = 2.00 51GRS = Y
51QP = 2.20 51QC = U3 51QTD = 2.00 51QRS = N
ZLF = 9.22 ZLR = 9.22
PLAF = 30.00 NLAF =-30.00 PLAR = 150.00 NLAR = 210.00
DIR3 = R DIR4 = F
ORDER = QVI
CLOEND= OFF 52AEND= 10.00 SOTFD = 30.00
Z3RBD = 5.00 EBLKD = 10.00 ETDPU = 2.00
EDURD = 4.00 EWFC = N
DMTC = 60 PDEMP = OFF GDEMP = OFF QDEMP = OFF
TDURD = 9.00 CFD = 60.00 3POD = 0.50 OPO = 52
Press RETURN to continue
50LP = 0.25
=>