SEL-311C Relay Instruction Manual Date Code 20060320
Application Settings for SEL-221 Series Relays
SEL-221H to SEL-311C Settings Conversion Guide
The following contact input assignments are made automatically by the
SEL-311C when setting APP = 221H. These assignments cannot be changed
unless setting APP is changed back to APP = 311C.
Default Contact Input Functions
IN101 = DT (Direct trip)
IN102 = PT (Permit trip)
IN103 = BT (Block trip)
IN104 = CL (Close breaker)
IN105 = 52A
IN106 = EXT (External event report trigger)