E.9
Date Code 20060320 Instruction Manual SEL-311C Relay
Compressed ASCII Commands
CEVENT Command—SEL-311C
If samples per cycle are specified as 16, the analog data are displayed at 1/16-
cycle intervals and digital data at 1/4-cycle intervals for filtered data; all data
are displayed at 1/16-cycle intervals for raw data. The digital data are
displayed as a series of hex ASCII characters. The relay displays digital data
only when they are available. When no data are available, the relay sends only
the comma delimiter in the digital data field.
If the specified event does not exist, the relay responds:
<STX>"No Data Available","0668"<CR><ETX>
The “Names of elements in the relay word separated by spaces” field is
shown below for the SEL-311C.
"EN TRP TIME COMM SOTF RCRS RCLO 51 A B C G ZONE1 ZONE2 ZONE3 ZONE4 M1P M1PT Z1G Z1GT
M2P M2PT Z2G Z2GT Z1T Z2T 50P1 67P1 67P1T 50G1 67G1 67G1T 51G 51GT 51GR LOP ILOP
ZLOAD ZLOUT ZLIN LB1 LB2 LB3 LB4 LB5 LB6 LB7 LB8 LB9 LB10 LB11 LB12 LB13 LB14 LB15
LB16 RB1 RB2 RB3 RB4 RB5 RB6 RB7 RB8 RB9 RB10 RB11 RB12 RB13 RB14 RB15 RB16 LT1 LT2
LT3 LT4 LT5 LT6 LT7 LT8 LT9 LT10 LT11 LT12 LT13 LT14 LT15 LT16 SV1 SV2 SV3 SV4 SV1T
SV2T SV3T SV4T SV5 SV6 SV7 SV8 SV5T SV6T SV7T SV8T SV9 SV10 SV11 SV12 SV9T SV10T
SV11T SV12T SV13 SV14 SV15 SV16 SV13T SV14T SV15T SV16T MAB1 MBC1 MCA1 MAB2 MBC2
MCA2 CVTBL SOTFT MAG1 MBG1 MCG1 MAG2 MBG2 MCG2 DCHI DCLO BCW BCWA BCWB BCWC FIDEN
FSA FSB FSC SG1 SG2 SG3 SG4 SG5 SG6 OC CC CLOSE CF TRGTR 52A 3PO SOTFE VPOLV 50L PDEM
GDEM QDEM TRIP 50QF 50QR 50GF 50GR 32QF 32QR 32GF 32GR 32VE 32QGE 32IE 32QE F32I
R32I F32Q R32Q F32QG R32QG F32V R32V * * IN106 IN105 IN104 IN103 IN102 IN101 ALARM
OUT107 OUT106 OUT105 OUT104 OUT103 OUT102 OUT101 M3P M3PT Z3G Z3GT M4P M4PT Z4G
Z4GT Z3T Z4T 50P2 67P2 67P2T 50P3 67P3 67P3T 50G2 67G2 67G2T 50G3 67G3 67G3T * * 51P
51PT 51PR Z1X 59VA MAB3 MBC3 MCA3 MAG3 MBG3 MCG3 27S 59S * 59VP 59VS SF 25A1 25A2
RCSF OPTMN RSTMN * * 79RS 79CY 79LO SH0 SH1 SH2 SH3 SH4 MAB4 MBC4 MCA4 MAG4 MBG4 MCG4
* * XAG1 XBG1 XCG1 XAG2 XBG2 XCG2 XAG3 XBG3 XCG3 XAG4 XBG4 XCG4 OSTI OSTO OST 50ABC
X5ABC X6ABC OSB OSB1 OSB2 OSB3 OSB4 UBOSB 50G4 67G4 67G4T * MPP1 MABC1 MPP2 MABC2
50Q1 67Q1 67Q1T 50Q2 67Q2 67Q2T 59N1 59N2 50Q3 67Q3 67Q3T 50Q4 67Q4 67Q4T 59Q 59V1
51Q 51QT 51QR * * Z2PGS 67QG2S BTX Z3XT DSTRT NSTRT STOP Z3RB KEY EKEY ECTT PTRX UBB1
UBB2 UBB WFC PT PTRX1 PTRX2 27A 27B 27C 59A 59B 59C 3P27 3P59 27AB 27BC 27CA 59AB
59BC 59CA * * OUT201 OUT202 OUT203 OUT204 OUT205 OUT206 OUT207 OUT208 OUT209 OUT210
OUT211 OUT212 MPP3 MABC3 MPP4 MABC4 IN208 IN207 IN206 IN205 IN204 IN203 IN202 IN201
RMB8A RMB7A RMB6A RMB5A RMB4A RMB3A RMB2A RMB1A TMB8A TMB7A TMB6A TMB5A TMB4A TMB3A
TMB2A TMB1A RMB8B RMB7B RMB6B RMB5B RMB4B RMB3B RMB2B RMB1B TMB8B TMB7B TMB6B TMB5B
TMB4B TMB3B TMB2B TMB1B LBOKB CBADB RBADB ROKB LBOKA CBADA RBADA ROKA 81D1 81D2 81D3
81D4
81D5 81D6 27B81 * 81D1T 81D2T 81D3T 81D4T 81D5T 81D6T * * ","yyyy"
These names are listed in Table 9.5. Lists for other relay models may be
derived from the appropriate tables in Section 9, using the above format.
A typical HEX-ASCII Relay Word is shown below:
100000049249000000000000000000000000000002000000000000000000000000240000800000C00001
00000000000000000000000000
"TARGETS" = the front-panel tripping targets
"IA", "IB", "IC",
"IP", "IG", "3I2"
= the fault current
"TRIG" = the trigger record
z = ">" for the trigger row, "*" for the fault
current row and empty for all others. If
the trigger row and fault current row are
the same, both characters are included
(e.g.,
">*").
"HEX-ASCII Relay Word" = the hex ASCII format of the Relay Word.
The first element in the Relay Word is the
most significant bit in the first character.