6.5
Date Code 20120126 Instruction Manual SEL-2032 Communications Processor
Database
Region Descriptions
0037h REMOTE_BIT_REG int For details on the Remote Bit Control
register (see Figure 6.5)
0038h REMOTE_BITS int Directly operate all 8 remote bits.
Lower byte corresponds to bits: bit 0
is R8, bit 1 is R7, … bit 7 is R1. The
upper byte must be the complement of
the lower byte for command to be accepted.
0039h _YEARS int Years in the century. 0–99
003Ah _HOURS int Hours in the day. 0–23
003Bh _MINS int Minutes in the hour. 0–59
003Ch _SECS int Seconds in the minute. 0–59
0100h PC1_FID char[40] Firmware identification string
of the plug-in protocol card in Port 17
0128h PC1_SERVICES int[2] Indicates what services are supported by
both the SEL-2032 and the protocol card
in Port 17. The first register is always 0.
The second register uses the following bits:
Bit 0: Card-initiated Virtual Terminal
Bit 1: SEL-2032-initiated Virtual
Terminal
Bit 2: Card-initiated File Transfers
Bit 3: SEL-2032-initiated File Transfers
Bit 4: Card-initiated Control Operations
Bit 5: SEL-2032-initiated Control
Operations
Bit 6: SEL-2032 can force card into
SELBOOT mode
Bit 7: Card-initiated Time Sync.
Bit 8: SEL-2032-initiated Time Sync.
Bit 9: Card can force SEL-2032 into
SELBOOT mode
012Ah PC1_STATUS int Bit-mapped integer that indicates protocol
card status:
Bit 0: Card alive and initialized
Bit 1: Card self-test failure
Bit 2: Card network port failure
Bit 3: Settings error
Bit 4: Card running in
SELBOOT mode
Bit 7: Card is in low resource condition
(e.g., low memory)
Bit 15: Card is no longer accessing
shared-memory; card has probably failed
012Bh PC1_CONFIG int Set to 0 if no protocol card is
recognized in Port 17; set to 1
if protocol card is recognized.
012Ch PC1_STEST_ERR int Contains self-test error code from
protocol card. See the protocol card
instruction manual for interpretation.
0200h PC2_FID char[40] Firmware identification string
of the protocol card in Port 18.
Table 6.2 Global Region (Sheet 2 of 3)
Starting
Address
Data Item Label
Data
Type
Notes
Courtesy of NationalSwitchgear.com