7.11
Date Code 20120126 Instruction Manual SEL-2032 Communications Processor
Settings
Automatic Message (SET A) Settings
setting the SEL-2032 to the lowest likely connection rate, typically 2400 baud.
Alternatively, you can enable RTS/CTS or XON/XOFF flow control between
the SEL-2032 and the modem.
To use hardware flow control, set RTS_CTS = Y on the modem port. Only use
this setting if the RTS and CTS control lines are wired between the SEL-2032
and the modem. The modem should default to use hardware flow control.
Alternatively, to use software flow control, set XON_XOFF=Y on the modem
port and modify the MSTR setting to enable XON/XOFF handshaking within
the modem. Refer to your modem data sheet to determine the appropriate code
for your modem.
Many external modems do not behave well if they receive non-modem
messages while they are not connected. For this reason, you should connect
the Data Carrier Detect output of the modem to the SEL-2032 so
transmissions to the modem can be prevented. If you have the modem
connected to Port 1 or 9 of an SEL-2032, you can connect DCD and RTS/CTS
flow control signals to the SEL-2032. If you are connected to any other port of
a SEL-2032, connect the modem DCD output to the CTS input of the
SEL-2032 and set CD_CTS to Yes. Of course, with this connection you will
not be able to use RTS/CTS flow control.
Another thing to consider when using modems is how to terminate the
connection. If you simply hang up, the SEL-2032 is left in whatever state you
were in. This could be a state to which you cannot call back. To avoid this, you
should do two things:
When a modem is on a Master port, always exit transparent
connections and issue the QUIT command to terminate the
connection. This way, you always leave the SEL-2032 in a
known state.
Set the port TIMEOUT setting to something other than 0. If
you do leave the SEL-2032 in an undesired state, it will return
to a basic Access Level 0 state after the TIMEOUT time, as if a
QUIT command had been issued.
Automatic Message (SET A) Settings
Use the SET A command to set the SEL-2032 to:
Automatically buffer unsolicited messages the SEL-2032
receives.
Automatically print those unsolicited messages, and clear the
buffer after printing if you desire.
Automatically issue operate messages based on operating
elements.
Automatically collect Sequential Events Recorder (SER) data.
Automatically collect synchrophasor data from SEL IEDs.
Define startup strings for connected devices so the SEL-2032
can communicate automatically with those devices.
Create messages to send to other devices and define conditions
that trigger those messages (messages are commands, data, or
both).