3.11
Date Code 20120126 Instruction Manual SEL-2032 Communications Processor
Job Done Examples
Example 2: Using the SEL-2032 as a Port Switch
*>>PORT 1 <Enter>
Transparent Communications to Port 1 established
<Enter>
=
Figure 3.8 Initiate Transparent Communications
You can now communicate with the relay attached to Port 1 as
though your terminal were directly connected to the relay. The
relay will be at Access Level 0, as indicated by the “=” prompt.
If you do not see the “Transparent Communication
Established” message or the relay prompt, check the cable
connection and the relay status. See Section 10: Testing and
Troubleshooting for more detailed information.
Step 3. Use the ACCESS command and relay password to get to
Access Level 1. At the “=>” relay prompt, issue the IRIG
command. IRIG directs the relay to read the demodulated
IRIG-B time-code input on the AUX input power panel port. If
the relay reads the time code successfully, the relay updates the
internal clock/calendar time and date and transmits a message
with relay ID string, date, and time. If no IRIG-B signal is
present, or the code cannot be read successfully, the relay sends
the error message “IRIG B DATA ERROR.” If you receive an
error message, check the cable connection between the
SEL-2032 and the relay AUX input port and consult
Section 10: Testing and Troubleshooting.
Issue the SHOWSET command (SHO for short) to view the
relay settings. You should see relay setting information similar
to that shown in Figure 3.9.
=>SHO <Enter>
Settings for group 1
Example 21.6 kV Feeder - S/N 93245011
CTR =120.00 PTR =180.00
R1 =0.58 X1 =1.50 R0 =1.44 X0 =4.56
RS =0.00 XS =0.00 LL =2.42
DATC =15 PDEM =12.00 QDEM =12.00 NDEM =0.99
79OI1=60 79OI2=600 79OI3=900 79OI4=0
79RST=1800 M79SH=00000
50C =99.99 27L =0.00 27H =0.00 27C =2 TCI =0
50Q =99.99 50QT =0
51QP =6.00 51QTD=15.00 51QC =3 51QRS=N
50NL =20.01 50NLT=2 50NH =99.99
51NP =1.50 51NTD=2.00 51NC =3 51NRS=N
50L =99.99 50LT =0 50H =39.99
51P =6.00 51TD =6.00 51C =3 51RS =N
52APU=1200 52ADO=0 TSPU =0 TSDO =0
TKPU =0 TKDO =0 TZPU =0 TZDO =0
PRESS RETURN ? <Enter>
SELogic Equations
S(123) =
A(12) =
B(12) =50NLT
C(12) =50NL
D(12) =
E(34) =79RS+79CY+52AT
F(34) =IN6
G(34) =
H(34) =
J(1234) =
K(1234) =
L(1234) =
A1(1234)=TF
A2(1234)=NDEM
PRESS RETURN ? <Enter>