B.4
SEL-2032 Communications Processor Instruction Manual Date Code 20120126
Firmware Upgrade Instructions
Upgrade Procedure
Step 5. Complete the appropriate set of steps below:
SEL-203
x
a. Type the REC command.
b. Respond by entering Y at the confirmation prompt.
c. When the SEL-203x is ready to receive the new code, it
prompts you to press any key to initiate the firmware
download.
d. The SEL-203x expects the file transfer to start within
approximately 10 seconds; otherwise the transfer will
fail.
e. Press a key and then use an Xmodem file transfer to
send the new SEL-203x code.
SEL-27xx
a. Type the REC n command, where n is the protocol card
port (e.g., if the card is on Port 17, then enter REC 17).
b. Respond by entering Y to the confirmation prompt.
c. When the SEL-203x is ready to receive the new code, it
prompts you to press any key to initiate the firmware
download.
d. Press a key and then use an Xmodem file transfer to
send the new protocol card code.
SEL-27xx SELBOOT code
a. Type the REC boot n command, where n is the
protocol card port (e.g., if the card is on Port 17, then
enter REC boot 17).
b. Respond by entering Y at the confirmation prompt.
c. When the SEL-203x is ready to receive the new code, it
prompts you to press any key to initiate the firmware
download.
d. The SEL-203x expects the file transfer to start within
approximately 10 seconds; otherwise the transfer will
fail.
e. Press a key and then use an Xmodem file transfer to
send the new SEL-203x SEL
BOOT code.
SEL-203
x
SELBOOT code
a. Type the REC boot command.
b. Respond by entering Y at the confirmation prompt.
c. When the SEL-203x is ready to receive the new code, it
prompts you to press any key to initiate the firmware
download.
d. The SEL-203x expects the file transfer to start within
approximately 10 seconds; otherwise the transfer will
fail.
e. Press a key and then use an Xmodem file transfer to
send the new SEL-203x SEL
BOOT code.