Program memory modules / Interface modules
Hardware - SIMADYN D 8-33
Edition 04.2011
8
8.7.4 Connector assignment
To connect the interface module to the SIMADYN D / SIMATIC TDC
components use cable SC62 or SC64 (for further informations see the
documentation of the SIMADYN D / SIMATIC TDC components).
Terminal 120 V Channel No.
11
21
31
41
51
61
71
81
Center contact
Center contact
Center contact
Center contact
Center contact
Center contact
Center contact
Center contact
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
12
22
32
42
52
62
72
82
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
NC contact
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
14
24
34
44
54
64
74
84
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
NO contact
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Channel 8
Table 8-8 Assignment of the binary inputs of interface module SB70, terminal block X2
The minimun conductor cross section for the terminal block X2 is
0,2mm², the maximum conductor cross section is 2,5 mm².
flat connector X1
Binary inputs,
terminal block X2
Conductor cross
section
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents

Other manuals for Siemens SIMADYN D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMADYN D and is the answer not in the manual?

Siemens SIMADYN D Specifications

General IconGeneral
BrandSiemens
ModelSIMADYN D
CategoryControl Systems
LanguageEnglish

Related product manuals