General technical data
1-10 Hardware - SIMADYN D
Edition 08.2005
1.1.14 Mounting clearances
The following minimum clearances must be maintained if SIMADYN D
subracks are mounted one on top of the other:
(For 2200 × 600 × 600 mm cabinets)
Front view Side view
Access level
EG
> 50 mm
> 50 mm
> 50 mm
> 50 mm
EG
ZG
Air intake
Discharged
air
Air deflection plate
Air intake
Discharged
air
min.120 mm
min.120 mm
min. 75 mm