General technical data
Hardware - SIMADYN D 1-13
Edition 08.2005
1
Power supply potentials
For SIMADYN D, the grounds of all secondary voltages must be
connected together and connected to the subrack housing and grounded;
this enhances the discharge of noise signals and voltages.
230/115 V AC
24 V DC
PE
Housing
+ 5 V
+ 15 V
- 15 V
Ground
Using clocked power supplies
If a clocked power supply is used for the 24V supply, the rated output of
the clocked power supply units must be designed for the inrush current of
SIMADYN D (the factor is 200 % of the rated current). Otherwise, the
clocked power supply can ramp-up along the short-circuit current limiting
and undefined conditions can occur.
1.1.17 Subracks
The subracks must be connected to the grounding/potential bonding
rail using the shortest possible 6mm
2
cable.
All of the boards must be screwed into subracks. This is also required
during the commissioning phase!
Empty slots must be provided with SIMADYN D slot covers.
If modules are inserted in an adapter during the commissioning
phase, the front panel must be electrically connected to the housing
through the shortest possible path.
Modules may neither be removed nor inserted under voltage.
The connectors for serial interfaces must be screwed to the front
panel.
The maximum temperature of the air drawn-in by the subrack is 55ºC.
The subrack must be mounted so that air can freely circulate. It must
be ensured that heat cannot build-up (no hotspots).
The air drawn-in by the subrack must be as dust-free as possible.