General technical data
Hardware - SIMADYN D 1-9
Edition 08.2005
1
1.1.11 Protective grounding
The protective ground is connected via the protective conductor (PE) at
the cabinets and components. For SIMADYN D, the potential bonding
conductor/cable does not have a protective conductor function. For
SIMADYN D it is required for reliable operation and noise suppression.
The protective conductor must be routed in accordance with DIN VDE
0100 and DIN VDE 0160.
For subracks, the protective conductor cross-section must be
6 mm
2
and for cabinets, 10 mm
2
.
1.1.12 Radios
It is not permissible to use radios > 2W close to SIMADYN D.
For low-rating radios, a distance of > 1m must be maintained between
the radio and SIMADYN D.
1.1.13 Cabinet
All SIMADYN D components must be mounted in a metal cabinet
Each cabinet must have a ground/potential bonding rail, which is
connected to the cabinet frame at both ends.
All SIMADYN D subracks must be connected to the
grounding/potential bonding rail through a 6 mm
2
cable which should
be as short as possible. The connection via the PE connection of the
power supply is not sufficient.
Non-damped contactors may not be used in a cabinet with SIMADYN
D components.
If non-damped contactors are used in a cabinet next to SIMADYN D,
then the cabinets must be separated by a metal partition.
All of the cabinets associated with multi-motor SIMADYN D drives
must be connected through a potential bonding conductor with at least
a 16 mm
2
cross-section (the customers PE connection is not
sufficient).
Each cabinet in which SIMADYN D components are installed/mounted
must have a screen rail. Serrated rails are suitable. The screen rail
must be connected directly to the cabinet frame.
No gas discharge lamps may be used in the cabinet.
The screens of incoming cables must be connected directly to the
screen rail.
The cabinets must be designed so that air can circulate freely within
them.