Communications support modules
Hardware - SIMADYN D 6-7
Edition 12.2004
6
6.1.1.3 Connecting diagram
L bus
CS7
26pin
SS4
9pin
SS5
SS52
9pin
SC57
l=5m
Cable 1
COM1/2
Operator
control unit
(PC)
9 pin
l=0.5m
Cable 2
.
9 pin
26 pin
SM8
Partial connector set
Connector assignment SS4
RS 232
TxD=4
RxD=17
Grd=9
RS 485 (USS-Bus)
+RS485P =5
-RS485N =17
Grd=9
D-Sub,
high density
Connector assignment SS5
RS 232 (Monitor)
TxD=7
RxD=2
Grd=5
RS 485 (PROFIBUS)
+Tx/Rx-Sig. =3
-Tx/Rx-Sig. =8
Grd=5
SM5
Partial connector set
Connector assignment SS52
RS 232 (Monitor)
TxD=7
RxD=2
Grd=5
RS 485 (PROFIBUS)
+Tx/Rx-Sig. =3
-Tx/Rx-Sig. =8
Grd=5
SM5
Partial connector set
D-Sub
D-Sub
DUST/USS
PROFIBUS FMS
PROFIBUS DP
or
or
or
Fig. 6-2 Connecting communication modules and cables