Commissioning and Diagnostics
6-40
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Power module error type s
The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-12 Power module error types
Power modules electronic
modules
Error type Meaning Remedy
PM-E 24--48
VDC/
120--230 VAC
PM-E 24
VDC
PM-E
24--48 VDC
17
D
10001: Encoder or
load voltage missing
No supply voltage,
or inadequate
supply v oltage.
Correct the process
wiring. Check the
supply v oltage.
-- -- -- 18
D
10010: Fuse defect Thefuseinthe
power module has
tripped.
Replace the fuse.
Digital electronic module error types
Table 6-13 Digital electronic module error types
Digital electronic
modules
Error type Meaning Remedy
2DI 2 4 VDC High
Feature
1
D
00001: Short-circuit Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Correct the process
wiring (sensor
wiring).
4DI 2 4 VDC High
Feature
1
D
00001: Short-circuit
(in connection with
IM151-1 BASIC /
IM151-1 STANDARD,
as of
6ES7 151-1AA02 0AB0,
IM151-1 FO
STANDARD, as of
6ES7 151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
Short circuit of the
sensor supply. The
diagnostic message
is issued on channel
0 and applies to the
whole module.
Correct the process
wiring (sensor
wiring).
26
D
11010: External
error/fault
(in connection with
IM151-1 STANDARD, to
6ES7 151-1AA01-0AB0
or IM151-1 FO
STANDARD, to
6ES7 151-1AB00-0AB0)