Commissioning and Diagnostics
6-41
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Table 6-13 Digital electronic module error types
Digital electronic
modules
RemedyMeaningError type
4DI 2 4--48 VUC High
Feature
26
D
11010: External
error/fault
Line to the actuator
interrupted.
Correct the process
wiring.
No supply voltage, or
inadequate supply
voltage.
Correct the process
wiring. Check the
supply v oltage.
Fuse triggered. Replace the fuse.
2DO 24 VDC/0.5 A
High Feature
2DO 24 VDC/2 A High
1
D
00001: Short-circuit Short circuit of the
actuator supply to
ground.
Correct the process
wiring.
2
D
O
2
4
V
D
C
/
2
A
H
g
h
Feature
6
D
00110: Wire break Line to the actuator
interrupted.
4DI NAMUR 1
D
00001: Short-circuit Short circuit in signal
line to sensor
Correct the process
wiring
Defective encoder Replace the sensor
Wrong encoder type
set
Correct the
parameter
assignment
Load impedance too
low.
Use a sensor with
increased
impedance.
6
D
00110: Wire break Signal line to a
sensor interrupted.
Correct the process
wiring
Defective encoder Replace the sensor
Wrong encoder type
set
Correct the
parameter
assignment.
Load impedance too
low.
Use a sensor with
increased
impedance.
9
D
01001: Error Internal module error
occurred.
Replace the module
Sensor signal flutters. Eliminate cause
16
D
10000: Parameter
assignment error
Parameter
assignment error
Correct the
parameter settings
26
D
11010: External
/
f
t
Sensor error. Replace the sensor
error/fault
Changeover contact
error.
Correct the process
wiring