Digital Electronic Modules
11-75
ET 200S Distributed I/O System
EWA-4NEB 780602402-12
Status, interrupts, diagnostics
Status display Green LED pro
Channel
Diagnostic functions No
Data for selection of an actuator
Output voltage
•
For signal ”1” min. L (--1.5 V)
Output current (per chan-
nel)
•
For signal ”1”
-- Rated value
-- Permitted range
2A
0.1mAto2.2A
•
For signal ”0” (residual
current)
max. 3 mA
Output delay (with ohmic
load)
•
”0” to ”1” transition Max. 15 ms
•
”1” to ”0” transition Max. 15 ms
Zero crossover Max. 25 V
Motor starter size
•
to 40°C Max. size as per
NEMA: 5
•
to 60°C Max. size as per
NEMA: 4
Lamp load max. 100 W
Connecting 2 outputs in
parallel
•
For redundant triggering
of a load
Yes (per module)
•
To increase
performance
No
Actuation of a digital input possible
Switching frequency
•
with ohmic load Max. 10 Hz
•
with inductive load Max. 0.5 Hz
•
With lamp load Max. 1 Hz
Short-circuit protection of
the output
Yes,viafuseinpow-
er module
* Total current of outputs (per module)
Temperature
Total current
per module
1A 1.5A 2A
60 °C
50 °C
40 °C