Line Modules Booksize
3.5 Smart Line Modules (16 kW and 36 kW) with internal air cooling
Equipment Manuel for Booksize Power Modules
3-72 Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
3.5.7 Technical specifications
Table 3-36 Technical specifications for Smart Line Modules in booksize format with internal air cooling
Internal air cooling 6SL3130– 6TE21-6ABx 6TE23-6ABx
Rated power kW 16 36
Supply:
Rated power (S1)
1
S6 infeed
Power rating (S6-40%)
1
Peak power rating
1
kW (Pn)
kW (Ps6)
kW (Pmax)
16
21
35
36
47
70
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
16
35
36
70
Connection voltages:
Line voltage
Line frequency
Electronics power supply
V
AC
Hz
V
DC
3AC 380 -10% to 3AC 480 +10% (-15% < 1 min)
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 – 750
820 ± 2%
360 ± 2%
Supply currents:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
26
21 / 19
27
54 /45
58
46 / 42
60
107 / 89
Output currents at 600 V
DC
:
Rated current
at S6-40%
peak current
A
DC
A
DC
A
DC
27
35
59
60
79
117
DC link busbar current carrying capacity A
DC
100 100
24 V busbar current carrying capacity A
DC
20 20
Electronics current consumption A
DC
1.1 1.5
Total power loss
(including electronic losses)
2
W 191.4 406
Max. ambient temperature without derating °C 40 40
Max. ambient temperature with derating °C 55 55
DC link capacitance μF 705 1410
Charging limit μF 20 000 20 000
Power factor cos ϕ 1 1
Efficiency ƞ 0.99 0.99
Cooling method Internal fan Internal fan
Sound pressure level dB(A) <60 <65
Cooling air requirement m
3
/h 56 112
Rated voltage for rated data 3 AC 380 V
Weight kg 7 10
1
The specified values apply for 380 V
2
For an overview, see the power loss tables in Cabinet Design