EasyManua.ls Logo

Siemens SINAMICS Series - 7 Cabinet Configuration and EMC Booksize; Information; General

Siemens SINAMICS Series
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
7-1
Cabinet Configuration and EMC Booksize
7
7.1 7.1 Information
7.1.1 General
The SINAMICS S components are designed in accordance with degree of protection IP20 to
EN 60529 and as open-type devices to UL 50. This ensures protection against electric
shocks. To ensure protection against mechanical stress and climatic conditions too, the
components should only be operated in housing/cabinets/rooms that fulfill at least degree of
protection IP54 and, as enclosure types, are designed to UL 50.
Prefabricated MOTION CONNECT cables are recommended.
The Safety-Integrated safety function:
The components must be protected against conducted contamination (e.g. by installing them
in a cabinet with degree of protection IP54).
Provided that conducted interference can be prevented at the installation site, the degree of
protection for the cabinet can be decreased accordingly.
Low-voltage switchgear and controlgear assemblies
Part 1: Type-tested and partially type-tested low-voltage switchgear assemblies
If the SINAMICS S drive line-up is used for the electrical equipment of machines, the
applicable requirements of EN 60204-1 must also be adhered to.
Safety of machinery
Electrical equipment of machines
Part 1: General requirements
All information for device selection in this section applies to
Operation in a TN system
Operating voltage range 360 V 3AC to 440 V 3AC