Cabinet Configuration and EMC Booksize
7.5 Information about electromagnetic compatibility (EMC) and cable laying
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
7-21
7.5.2 Cable Shielding and Routing
In order to comply with the EMC requirements, certain cables must be routed apart from
other cables and from certain components. To full EMC requirements, the following cables
must be used with shields:
• Power supply cables from line filter via line reactor to Line Module
• All motor cables (if necessary, including cables for motor holding brake)
• Cables for "fast inputs" of the Control Unit
• Cables for analog direct voltage/current signals
• Signal cables for sensors
• Cables for temperature sensors
The EMC measures described above ensure CE compliance with the EMC Directive.
Alternative measures (e.g. routing behind mounting plates, suitable clearances) can also be
used provided they have similar results. This excludes measures that relate to the design,
installation, and routing of motor power cables and signal cables. If unshielded cables are
used between the line connection point and line filter, make sure that no interfering cables
are routed in parallel.
The cable shields must be connected as close to the conductor terminal connections as
possible to ensure a low-impedance connection with cabinet ground. For Siemens power
cables in which the shield is connected to the connector shell (see relevant catalog), this is a
sufficiently good shield contact.
With components that do not have any special shield connection or where the shield
connection is not sufficient, the cable shields can be connected to the metal mounting plate
using hose clamps and toothed rails. The cable length between the shield contact point and
the terminals for cable conductors must be kept as short as possible.
Shield contact plates with pre-prepared clip contacts are available for contacting the shields
for power cables of Line Modules and Motor Modules. Up to a module width of 100 mm,
these plates are part of the scope of supply of the components, or they are integrated in the
connector.
All cables inside the cabinet must be connected as closely as possible to parts connected
with cabinet ground, such as a mounting plate or cabinet wall. Ducts made of sheet steel or
routing cables between between steel sheets (e.g. between the mounting plate and back
wall) should provide adequate shielding.
Avoid, where possible, routing unshielded cables, connected to the drive line-up, in the
immediate vicinity of noise sources, e.g. transformers. Signal lines (shielded and unshielded)
connected to the drive line-up, must be routed as far as possible away from strong external
magnetic fields (e.g. transformers, line reactors). In both cases, a distance of ≥ 300 mm is
usually sufficient.

Table of Contents

Other manuals for Siemens SINAMICS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS Series and is the answer not in the manual?

Siemens SINAMICS Series Specifications

General IconGeneral
Product LineSINAMICS
Cooling MethodAir-cooled, Liquid-cooled
Voltage Range200 V to 690 V
Power Range0.12kW - 250kW
Communication InterfacesPROFINET, PROFIBUS, Ethernet
Control ModesVector control, V/f control
Protection ClassIP20
TypeVariable Frequency Drives (VFD)

Related product manuals