Cabinet Configuration and EMC Booksize
7.6 Connection methods
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
7-25
7.6 7.6 Connection methods
7.6.1 Spring-Loaded Terminals/Screw Terminals
Connectable conductor cross-sections of spring-loaded terminals
Table 7-12 Spring-loaded terminals
Spring-loaded terminal type
Connectable conductor
cross-sections
Flexible
With wire end ferrule, without plastic sleeve
With wire end ferrule, with plastic sleeve
0.14 mm
2
to 1.5 mm
2
0.25 mm
2
to 1.5 mm
2
0.25 mm
2
to 0.5 mm
2
Insulation stripping length 7 mm
1
Tool Screwdriver 0.4 x 2.0 mm
Connectable conductor
cross-sections
Flexible 0.08 mm
2
to 2.5 mm
2
Insulation stripping length 8 to 9 mm
2
Tool Screwdriver 0.4 x 2.0 mm
Connectable conductor cross-sections of screw terminals
Table 7-13 Screw terminals
Screw terminal type
Connectable conductor
cross-sections
Flexible
With wire end ferrule, without plastic sleeve
With wire end ferrule, with plastic sleeve
0.14 mm
2
to 1.5 mm
2
0.25 mm
2
to 1.5 mm
2
0.25 mm
2
to 0.5 mm
2
Insulation stripping length 7 mm
Tool Screwdriver 0.4 x 2.0 mm
1
Tightening torque 0.22 to 0.25 Nm
Connectable conductor
cross-sections
Flexible
With wire end ferrule, without plastic sleeve
With wire end ferrule, with plastic sleeve
0.2 mm
2
to 2.5 mm
2
0.25 mm
2
to 1 mm
2
0.5 mm
2
to 1 mm
2
Insulation stripping length 7 mm
Tool Screwdriver 0.6 x 3.5 mm
2
Tightening torque 0.5 to 0.6 Nm
Connectable conductor
cross-sections
Flexible
With wire end ferrule, without plastic sleeve
With wire end ferrule, with plastic sleeve
0.2 mm
2
to 2.5 mm
2
0.25 mm
2
to 1 mm
2
0.25 mm
2
to 1 mm
2
Insulation stripping length 9 mm
Tool Screwdriver 0.6 x 3.5 mm
3
Tightening torque 0.5 to 0.6 Nm