Line Modules Booksize
3.4 Smart Line Modules (5 kW and 10 kW) with internal air cooling
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
3-55
3.4.7 Technical Specifications
Table 3-27 Technical specifications for Smart Line Modules in booksize format with internal air cooling
Internal air cooling 6SL3130– 6AE15–0AAx 6AE21–0AAx
Rated power kW 5 10
Supply:
Rated power (S1)
1
S6 infeed
Power rating (S6-40%)
1
Peak power rating
1
kW (Pn)
kW (Ps6)
kW (Pmax)
5
6.5
10
10
13
20
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
kW
kW
5
10
10
20
Connection voltages:
Line voltage
Line frequency
Electronics power supply
V
AC
Hz
V
DC
3AC 380 -10% to 3AC 480 +10% (-15% < 1 min)
47 to 63
24 (20.4 - 28.8)
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
V
DC
V
DC
V
DC
510 – 750
820 ± 2%
360 ± 2%
Supply currents:
at 380 V
AC
at 480 V
AC
/528 V
AC
at 480 V; S6-40%)
Peak current (at 400 V
AC
/480 V
AC
)
A
AC
A
AC
A
AC
A
AC
12
9.3/8.5
12
22/18.5
24
18/16.5
24
44/37
Output currents at 600 V
DC
:
Rated current
at S6-40%
peak current
A
DC
A
DC
A
DC
8.3
11
16.6
16.6
22
33.2
DC link busbar current carrying capacity A
DC
100 100
24 V busbar current carrying capacity A
DC
20 20
Electronics current consumption A
DC
1.0 1.3
Total power loss
(including electronic losses)
2
W 113 201.2
Max. ambient temperature without derating °C 40 40
Max. ambient temperature with derating °C 55 55
DC link capacitance μF 220 330
Charging limit μF 6000 6000
Power factor cos Ï• 1 1
Efficiency Æž 0.98 0.98
Cooling method Internal fan Internal fan
Sound pressure level dB(A) <60 <60
Cooling air requirement m
3
/h 29.6 29.6
Rated voltage for rated data 3 AC 380 V
Weight kg 4.68 4.78
1
The specified values apply to 380 V
2
For an overview, see the power loss tables in Cabinet Design.