DC link components Booksize
5.1 Braking Module Booksize
Equipment Manuel for Booksize Power Modules
Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
5-5
5.1.3.3 Braking resistor connection X1
Table 5-1 Terminal block X1
Terminal Name Technical specifications
1 Braking resistor connection R1
2 Braking resistor connection R2
Continued-short-circuit-proof
Max. connectable cross-section: 4 mm
2
Type: Screw terminal 4 (see Connection Methods)
5.1.3.4 X21 digital inputs/outputs
Table 5-2 Terminal block X21
Terminal Name
1)
Technical specifications
1 DI low: enable braking module
DI high: braking module inhibited
Edge change high -> low: fault
acknowledgement
DI low: braking resistor not activated
manually
DI high: braking resistor activated manually
(fast discharge)
Safety functions remain active, I*t protection
remains active
2
If X21.1 and 2 are activated simultaneously,
the braking module inhibit has priority.
Voltage: -3 V to 30 V
Typical current consumption: 10 mA at
24 V DC
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
3 DO high: no pre-warning for I*t shutdown
DO low: pre-warning for I*t shutdown (80%
of max. ON time reached)
4 DO high: ready for operation, no fault
DO low: fault; braking module inhibited
5
6
Ground
Max. load current per output: 100 mA
Continued-short-circuit-proof
Voltage: 24 V DC
Max. connectable cross-section 1.5 mm
2
Type: Screw terminal 1 (see Connection Methods)
1) DI: digital input; DO: digital output; M: Electronic ground
Note
Applying a high signal to terminal X21.1 inhibits the braking module. On a falling edge,
pending error signals are acknowledged.
The pre-warning for I*t monitoring is output as a high level on reaching 80% of the maximum
braking resistor ON time.
Only braking resistors approved by Siemens for this component are identified automatically.