6.1 Shielded terminal plates
Equipment Manuel for Booksize Power Modules
6-16 Manual, (GH2), Edition 06.2005, 6SL3097-2AC00-0BP2
Table 6-5 Electrical connection to shielded terminal plate for 200 mm module (e.g. with internal air cooling)
Unlock and remove the cover of the
terminal block.
Remove nuts M8 using a suitable tool. Secure the earthing cable with
screwdriver T25 and the power cable
with torque spanner M8/13 Nm.
Adjust the shock-hazard protection
using a suitable tool.
Attach the shock-hazard protection. Secure the shield clip to the shielded
terminal plate using a suitable tool.