12713020-002-2 Revision D – April 2004 SSU-2000 User’s Guide 291
TL1 Command Interface
RTRV-PRMTR-CLK:[tid]:[aid]:
ctag;
Valid aid code: ALL or S1A1 or S1A12
This command returns the settings for the clock designated
by the aid, or both clocks for ALL.
The format for each response message line is:
^^^"aid:warmup,mintau,maxtau,clkar" <cr lf>
where:
warmup = warmup delay time
mintau = starting time constant
maxtau = final time constant value in seconds for the
clock
clkar = current setting for the clock Auto-Return mode
[OFF|ON]
Table B-5. TL1 Retrieve Commands (Continued)