EasyManua.ls Logo

Woodward LS-5 v2 Series - Page 121

Woodward LS-5 v2 Series
448 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
reactive power condition for tripping
the monitoring function is TRUE.
Notes
This value refers to the "SyA. rated
react. power [kvar]" (parameter
1758).
3283 Delay step 1 2 0.10 to 99.99 s
[0.50 s]
If the QV monitoring conditions are
met, for the delay time con󰈡gured
here, an alarm "SyA. QV mon. 1" will
be issued and LogicsManager 07.29
becomes TRUE.
Notes
The decoupling function is only
activated if "SyA. decoupling"
(parameter 3295) is con󰈡gured to
"Step 1".
3284 Delay step 2 2 0.10 to 99.99 s
[1.50 s]
If the QV monitoring conditions are
met, for the delay time con󰈡gured
here, an alarm "SyA. QV mon. 2" will
be issued and LogicsManager 07.30
becomes TRUE.
Notes
The decoupling function is only
activated if "SyA. decoupling"
(parameter 3295) is con󰈡gured to
"Step 2".
3280 Alarm class 2 Class A/B/C/D/E/F/Control
[B]
The alarm class speci󰈡es what action
should be taken when at least one
delay has been exceeded.
Notes
For additional information refer to ╚═▷
“9.4.1 Alarm Classes”
3293 Self acknowledge 2 [Yes] The control unit automatically clears
the alarm if the fault condition is no
longer detected.
No The control unit does not
automatically reset the alarm when
the fault condition is no longer
detected.
The alarm must be acknowledged and
reset by manually pressing the
appropriate buttons or by activating
the LogicsManager output "External
acknowledgement" (via a discrete
input or via an interface).
3294 Monitoring lockable 2 Yes Monitoring for fault conditions is only
performed if Lock Monitoring Status
24.40 is false.
121LS-5 v2 Series37650
4 Con󰈡guration
4.3 Con󰈡gure Monitoring
Released

Table of Contents

Related product manuals