12958 Close CBA in MAN 2 Determined by
LogicsManager
[(0&1)&1]
Once the conditions of the
LogicsManager have been ful󰈡lled the
LS-5 closes the CBA, if no other LS-5
with higher priority likes to do the
same. (Provided the conditions for
dead bus closure or synchronization
are true.)
Notes
If a close or open command is active
but is blocked by another device with
higher priority the display shows "CBA
request".
Only in operation mode MANUAL.
No access in application mode
A05
.
12943 Open CBA unload 2 Determined by
LogicsManager
[(09.06& 1)&1]
Once the conditions of the
LogicsManager have been ful󰈡lled the
LS-5 opens the CBA with unloading, if
no other LS-5 with higher priority likes
to do the same.
Notes
If a close or open command is active
but is blocked by another device with
higher priority the display shows "CBA
request".
Only in operation mode AUTOMATIC.
No access in application mode
A05
.
12944 Open CBA immediately 2 Determined by
LogicsManager
[(09.04&1)&1]
Once the conditions of the
LogicsManager have been ful󰈡lled the
LS-5 opens the CBA immediately.
Notes
Only in operation mode AUTOMATIC.
No access in application mode
A05
.
12945 Enable close CBA 2 Determined by
LogicsManager
[(09.07&!08.07)&!
07.05]
Once the conditions of the
LogicsManager have been ful󰈡lled the
LS-5 closes the CBA, if no other LS-5
with higher priority likes to do the
same. (Provided the conditions for
dead bus closure or synchronization
are true.)
Notes
If a close or open command is active
but is blocked by another device with
higher priority the display shows "CBA
request".
Only in operation mode AUTOMATIC.
No access in application mode
A05
.