4.4.2.3.1 Synchronization CBA
ID Parameter CL Setting range
[Default]
Description
5730 Synchronization CBA 2 [Slip frequency] The LS-5 instructs the frequency
controller (e.g. easYgen) to adjust the
frequency in a way, that the
frequency of the variable system is
marginally greater than the target.
When the synchronizing conditions are
reached, a close command will be
issued. The slipping frequency is
positive to avoid reverse power.
Phase matching The LS-5 instructs the frequency
controller (e.g. easYgen) to adjust the
phase angle of the variable system to
that of the target, in view of turning
the phase dierence to zero.
Notes
This parameter has no impact on
Command Variables 02.28 Sync.
Check Relay and 02.29 Sync.
Condition.
5709 CBA sync. with sep. slip 2 On The easYgen(s) take the LS-5 slip
frequency separate oset
(easYgen-3400XT/3500XT version
1.13 and higher, parameter 6676).
[O ] The easYgen(s) take the slip
frequency oset (easYgen parameter
5502) of the GCBs.
Notes
This parameter is only visible if the
LS-5 'Synchronization CBA' (parameter
5730) is set to 'Slip frequency'.
This parameter is only valid if the
easYgen is in application mode
GCB/LS5
A02
and if the LS-5
'Synchronization CBA' (parameter
5730) is set to 'Slip frequency'.
The parameter 6676 is only
implemented in easYgen-3400XT/
3500XT version 1.13 and higher. In
combination with other devices the
parameter described here
5709 has
no impact.
5711 Pos. freq. dierential CBA
(Positive frequency dierential CBA)
2 0.00 to 0.49 Hz
[+0.18 Hz]
The prerequisite for a connect
command being issued for the CBA is
that the dierential frequency is below
the congured dierential frequency.
This setting is always in regards of
system A:
•
If the system B is the variable
system (i.e. generator), this
conguration is the maximum
allowed slip frequency then
160 LS-5 v2 Series 37650
4 Conguration
4.4 Congure Application