Terminal Description A
max
E 26 System B voltage - L3 120 Vac 2.5 mm²
F 27 480 Vac 2.5 mm²
G 28 System B voltage - N 120 Vac 2.5 mm²
H 29 480 Vac 2.5 mm²
Tab. 6: Voltage measuring - system B - terminal assignment
3.3.4.3.1 Parameter Setting '3Ph 4W' (3-phase, 4-wire)
System B windings
A L1
B
L2
C
L3
A1
A2
B2
B1
C1
C2
N
N
A L1
B
L2
C
L3
A1
A2
B6
B5
C5
C6
A5
A6
B2
B1
C1
C2
N
N
A L1
B
L2
C
L3
A1
A2
B6
B5
C5
C6
A5
A6
B2
B1
C1
C2
N
N
Fig. 39: System B windings - 3Ph 4W
Measuring inputs
Fig. 40: Measuring inputs - 3Ph 4W
Terminal assignment
3Ph 4W Wiring terminals
Rated voltage (range) 120 V (50 to 130 V
e󰈠.
)
480 V (131 to 480 V
e󰈠.
)
Measuring range
(max.)
0 to 150 Vac 0 to 600 Vac
Terminal A C E G B D F H
22 24 26 28 23 25 27 29
Phase L1 L2 L3 N L1 L2 L3 N
53LS-5 v2 Series37650
3 Installation
3.3 Setup Connections
Released