For dierent voltage systems, dierent wiring terminals have to be used.
Incorrect measurements are possible if both voltage systems use the same N terminal.
3.3.4.3.2 Parameter Setting '3Ph 3W' (3-phase, 3-wire)
System B windings
L2
L3
B2
B1
A1
A2
C1
C2
A L1
C
B
L2
L3
B2
B1
A5
A6
C1
C2
A L1
C
B
C5
C6
A1
A2
B6
B5
Fig. 41: System B windings - 3Ph 3W
Measuring inputs
Fig. 42: Measuring inputs - 3Ph 3W
Terminal assignment
3Ph 3W Wiring terminals
Rated voltage (range) 120 V (50 to 130 V
e.
)
480 V (131 to 480 V
e.
)
Measuring range
(max.)
0 to 150 Vac 0 to 600 Vac
Terminal A C E G B D F H
22 24 26 28 23 25 27 29
Phase L1 L2 L3 --- L1 L2 L3 ---
54 LS-5 v2 Series 37650
3 Installation
3.3 Setup Connections