Appendix
12 - 18
Table 12.1 User Constants (Continued)
No.
Name
(Display)
Factory
Setting
Setting No.
Name
(Display)
Factory
Setting
Setting
H1-05
Multi-function input (terminal 7)
(Terminal 7 Sel)
6 (4)
:
5
L2-01
Momentary power loss detection
(PwrL Selection)
0
H1-06
Multi-function input (terminal 8)
(Terminal 8 Sel)
8 (6)
:
5
L2-02
Momentary power loss ridethru time
(PwrL Ridethru t)
0.7
:
2
H2-01
Multi-function input (terminal 9-10)
(Terminal 9 Sel)
0
L2-03
Min. baseblock time
(PwrL Baseblock t)
0.5
:
2
H2-02
Multi-function input (terminal 25-27)
(Terminal 25 Sel)
1
L2-04
Voltage recovery time
(PwrL V/F Ramp t)
0.3
:
2
H2-03
Multi-function input (terminal 26-27)
(Terminal 26 Sel)
2
L2-05
Undervoltage detection level
(PUV Det Level)
190
:
3
H3-01
Signal level selection (terminal 13)
(Term 13 Signal)
0
L2-06
KEB deceleration rate
(KEB Frequency)
0.0
H3-02
Gain (terminal 13)
(Terminal 13 Gain)
100.0
L3-01
Stall prevention selection during accel
(StallP Accel Sel)
1
H3-03
Bias (terminal 13)
(Terminal 13 Bias)
0.0
L3-02
Stall prevention level during accel
(StallP Accel Lvl)
150
H3-04
Signal level selection (terminal 16)
(Term 16 Signal)
0
L3-03
Stall prevention limit during accel
(StallP CHP Lvl)
50
H3-05
Multi-function analog input (terminal 16)
(Terminal 16 Sel)
0
L3-04
Stall prevention selection during decel
(StallP Decel Sel)
1
H3-06
Gain (terminal 16)
(Terminal 16 Gain)
100.0
L3-05
Stall prevention selection during running
(StallP Run Sel)
1
H3-07
Bias (terminal 16)
(Terminal 16 Bias)
0.0
L3-06
Stall prevention level during running
(StallP Run Level)
160
H3-08
Signal level selection (terminal 14)
(Term 14 Signal)
2
L4-01
Speed agree detection level
(Spd Agree Level)
0.0
H3-09
Multi-function analog input (terminal 14)
(Terminal 14 Sel)
1F
L4-02
Speed agree detection width
(Spd Agree Width)
2.0
H3-10
Gain (terminal 14)
(Terminal 14 Gain)
100.0
L4-03
Speed agree detection level (+/)
(Spd Agree Lvl + )
0.0
H3-11
Bias (terminal 14)
(Terminal 14 Bias)
0.0
L4-04
Speed agree detection width (+/)
(Spd Agree Wdth + )
2.0
H3-12
Analog input filter time constant
(Filter Avg Time)
0.00
L4-05
Operation when frequency reference is missing
(Ref Loss Sel)
0
H4-01
Monitor selection (terminal 21)
(Terminal 21 Sel)
2
L5-01
Number of auto restart attempts
(Num of Restarts)
0
H4-02
Gain (terminal 21)
(Terminal 21 Gain)
1.00
L5-02
Auto restart operation selection
(Restart Sel)
0
H4-03
Bias (terminal 21)
(Terminal 21 Bias)
0.0
L6-01
Torque detection selection 1
(Torq Det 1 Sel)
0
H4-04
Monitor selection (terminal 23)
(Terminal 23 Sel)
3
L6-02
Torque detection level 1
(Torq Det 1 Lvl)
150
H4-05
Gain (terminal 23)
(Terminal 23 Gain)
0.50
L6-03
Torque detection time 1
(Torq Det 1 Time)
0.1
H4-06
Bias (terminal 23)
(Terminal 23 Bias)
0.0
L6-04
Torque detection selection 2
(Torq Det 2 Lvl)
0
H4-07
Analog output signal level selection
(AO Level Select)
0
L6-05
Torque detection level 2
(Torq Det 2 Lvl)
150
H5-01
Station address
(Serial Comm Adr)
1F
L6-06
Torque detection time 2
(Torq Det 2 time)
0.1
H5-02
Communication speed selection
(Serial Baud Rate)
3
L7-01
Forward torque limit
(Torq Limit Fwd)
200
H5-03
Communication parity selection
(Serial Com Sel)
0
L7-02
Reverse torque limit
(Torq Limit Rev)
200
H5-04
Stopping method after communication error
(Serial Fault Sel)
3
L7-03
Forward regenerative torque limit
(Torq Lmt Fwd Rgn)
200
H5-05
Communication error detection selection
:
1
(Serial Flt Dtct)
1
L7-04
Reverse regenerative torque limit
(Torq Lmt Rev Rgn)
200
L1-01
Motor protection selection
(MOL Fault Select)
1
L8-01
Protect selection for internal DB resistor
(DB Resistor Prot)
0
L1-02
Motor protection time constant
(MOL Time Const)
1.0
L8-02
Overheat pre-alarm level
(OH Pre-Alarm Lvl)
95
* 1. Not displayed for some models depending on software version No.
* 2. Setting unit and initial setting depend on Inverter capacity.
* 3. Setting for 200 V class Inverters. For 400 V class Inverters, double the value.
* 4. Not initialized. (Japanese standard specification is o2-09 = 0.)
12