4.7 Auto-Tuning
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 117
T1-03: Motor Rated Voltage (T1-01=3)
Sets the motor rated voltage according to the motor nameplate value. If the motor to be operated above its base speed,
enter the voltage at base speed here.
For better control precision around rated speed when using a vector control mode, it can be helpful to enter the no-load
voltage for the motor here. The motors “no-load voltage” refers to the voltage needed to operate the motor under no-load
conditions at rated speed. The no-load voltage can usually be found in the motor test report available from the
manufacturer. If no data is available, enter approximately 90% of the rated voltage printed on the motor nameplate. Note
that this might increase the output current reducing the overload margin.
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. For optimal performance, the motor rated current
should be between 50 and 100% of the drive rated current. Enter the current at the motor base speed.
T1-05: Motor Base Frequency (T1-01=3)
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used
or the motor is used in the field weakening area, enter the maximum frequency to E1-04 after Auto-Tuning is complete.
T1-06: Number of Motor Poles (T1-01=3)
Sets the number of motor poles according to the motor nameplate value.
T1-07: Motor Base Speed (T1-01=3)
Used to set the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is
used or the motor is used in the field weakening area, enter the speed at base frequency here.
T1-11: Motor Iron Loss (T1-01=3)
Provides iron loss information for determining the Energy Saving coefficient. T1-11 will first display a value for the
motor iron loss that the drive automatically calculated the when motor capacity was entered to T1-02. If the motor test
report is available, enter the motor iron loss value listed there.
No.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
Name Setting Range Default
T1-03 <1>
Motor Rated Voltage 0.0 to 255.5 V 200.0 V
No. Name Setting Range Default
T1-04 Motor Rated Current 10 to 200% of drive rated current E2-11
No. Name Setting Range Default
T1-05 Motor Base Frequency 0.0 to 200.0 Hz 50.0Hz
No. Name Setting Range Default
T1-06 Number of Motor Poles 2 to 48 4
No. Name Setting Range Default
T1-07 Motor Base Speed 0 to 24000 r/min 1450 r/min
No. Name Setting Range Default
T1-11 Motor Iron Loss 0 to 65535 W E2-11
SIEP_C710616_35.book 117 ペー 2015年11月30日 月曜日 午後2時2分