5.7 H: Terminal Functions
202 YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual
■ H3-14: Analog Input Terminal Enable Selection
When one of the multi-function digital input parameters is set for “Analog input enable” (H1- = C), the value set to
H3-14 determines which analog input terminals are enabled and which terminals are disabled when the input is closed.
All analog input terminals will be enabled all of the time if H1- is not set to C.
Setting 1: A1 only enabled
Setting 2: A2 only enabled
Setting 3: A1 and A2 only enabled
Setting 4: A3 only enabled
Setting 5: A1 and A3 only enabled
Setting 6: A2 and A3 only enabled
Setting 7: All analog input terminals enabled
■ H3-16 to H3-18 Terminal A1/A2/A3 Offset
Parameters H3-16 to H3-18 set the offset level of the selected input value to terminal A1, A2 or A3 that is equal to 0 Vdc
input. These parameters rarely need adjustment.
■
Multi-Function Analog Input Terminal Settings
See Table 5.30 for information on how H3-02, H3-10, and H3-06 determine functions for terminals A1, A2, and A3.
Note: The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values
when selecting and adjusting analog input functions.
Table 5.30 Multi-Function Analog Input Terminal Settings
Setting 0: Frequency Bias
The input value of an analog input set to this function will be added to the analog frequency reference value. When the
frequency reference is supplied by a different source other than the analog inputs, this function will have no effect. Use
this setting also when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Using A1 and A2 at the same time increases the frequency
reference by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog
input terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.
No. Name Setting Range Default
H3-14 Analog Input Terminal Enable Selection 1 to 7 7
No. Name Setting Range Default
H3-16 Terminal A1 Offset –500 to 500 0
H3-17 Terminal A2 Offset –500 to 500 0
H3-18 Terminal A3 Offset –500 to 500 0
Setting Function Page Setting Function Page
0
<1> This function is available in models CIMR-E4A0930 and 4A1200.
Frequency Bias 202 C PI Setpoint 204
1Frequency Gain 203 D Frequency Bias 204
2 Auxiliary Frequency Reference 1 203 E Motor Temperature (PTC input: A3 only) 204
3 Auxiliary Frequency Reference 2 203 F Through Mode 204
4 Output Voltage Bias 203 16 Differential PI Feedback 204
5 Accel/Decel Time Gain 203 17 <1> Motor Thermistor (NTC) 204
6 DC Injection Braking Current 203 1F Through Mode 204
7 Torque Detection Level 203 30 DriveWorksEZ Analog Input 1
204
8 Stall Prevention Level During Run 204 31 DriveWorksEZ Analog Input 2
9 Output Frequency Lower Limit Level 204 32 DriveWorksEZ Analog Input 3
B PI Feedback 204 –––
SIEP_C710616_35.book 202 ページ 2015年11月30日 月曜日 午後2時2分