B.3 Parameter Table
Parameter List
B
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 363
b4: Timer Function
b5: PI Control
b3-24
(1C0H)
Speed Search Method Selection
0: Current Detection Speed Search
1: Speed Estimation Speed Search
Default: 0
Min: 0
Max: 1
144
b3-25
(1C8H)
Speed Search Wait Time
Sets the time the must wait between each Speed Search restart attempt.
Default: 0.5 s
Min: 0.0 s
Max: 30.0 s
144
b3-27
(1C9H)
Start Speed Search Select
0: Triggered when a Run Command is Issued (Normal)
1: Triggered when an External Baseblock is Released
Default: 0
Min: 0
Max: 1
144
<9> Default setting value is dependent on the drive model (o2-04).
<10> Default setting is determined by the control mode (A1-02).
No.(Addr.) Name Description Setting Page
b4-01
(1A3H)
Timer Function On-Delay Time
Used to set the on-delay and off-delay times for a digital timer output (H2-=12). The output
is triggered by a digital input programmed to H1-=18)
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
144
b4-02
(1A4H)
Timer Function Off-Delay Time
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
144
No.(Addr.) Name Description Setting Page
b5-01
(1A5H)
PI Function Setting
0: PI Disabled
1: Output Frequency=PI Output 1
3: Output Frequency=Frequency Reference+PI Output 1
Default: 0
Min: 0
Max: 3
148
b5-02
(1A6H)
Proportional Gain Setting (P)
Sets the proportional gain of the PI controller.
Default: 1.00
Min: 0.00
Max: 25.00
148
b5-03
(1A7H)
Integral Time Setting (I)
Sets the integral time for the PI controller.
Default: 1.0 s
Min: 0.0 s
Max: 360.0 s
148
b5-04
(1A8H)
Integral Limit Setting
Sets the maximum output possible from the integrator as a percentage of the maximum output
frequency.
Default: 100.0%
Min: 0.0%
Max: 100.0%
148
b5-06
(1AAH)
PI Output Limit
Sets the maximum output possible from the entire PI controller as a percentage of the maximum
output frequency.
Default: 100.0%
Min: 0.0%
Max: 100.0%
148
b5-07
(1ABH)
PI Offset Adjustment
Applies an offset to the PI controller output. Set as a percentage of the maximum output
frequency.
Default: 0.0%
Min: -100.0%
Max: 100.0%
148
b5-08
(1ACH)
PI Primary Delay Time Constant
Sets a low pass filter time constant on the output of the PI controller.
Default: 0.00 s
Min: 0.00 s
Max: 10.00 s
148
b5-09
(1ADH)
PI Output Level Selection
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
Default: 0
Min: 0
Max: 1
149
b5-10
(1AEH)
PI Output Gain Setting
Sets the gain applied to the PI output.
Default: 1.00
Min: 0.00
Max: 25.00
149
b5-11
(1AFH)
PI Output Reverse Selection
0: Reverse Disabled
1: Reverse Enabled
When using setting 1, make sure reverse operation is permitted by parameter b1-04.
Default: 0
Min: 0
Max: 1
149
b5-12
(1B0H)
PI Feedback Loss Detection
Selection
0: Digital Output Only.
1: Feedback Loss Alarm
2: Feedback Loss Fault
3: Digital output only. Even if PI control is disabled by Digital Input.
4: Feedback Loss Alarm. Even if PI is disabled by Digital Input.
5: Feedback Loss Fault. Even if PI is disabled by Digital Input.
Default: 0
Min: 0
Max: 5
150
b5
-13
(1B1H)
PI Feedback Loss Detecti
on Level
Sets the PI feedback loss detection level as a percentage of the maximum output frequency.
Default: 0%
Min: 0%
Max: 100%
150
No.(Addr.) Name Description Setting Page
OLV/PMV/f
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
SIEP_C710616_35.book 363 ペー 2015年11月30日 月曜日 午後2時2分

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA E1000 and is the answer not in the manual?

YASKAWA E1000 Specifications

General IconGeneral
BrandYASKAWA
ModelE1000
CategoryController
LanguageEnglish

Related product manuals