B.6 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC SIEP C710616 35D YASKAWA AC Drive E1000 Technical Manual 403
No. Name Unit Default Settings
Model CIMR-E – 4A0414 4A0515 4A0675 4A0930 4A1200
o2-04 Drive Model Selection Hex. AA AC AE B0 B2
E2-11 Motor rated Output kW 220 250 355 500 630
b3-04 V/f Gain during Speed Search % 60 60 60 60 60
b3-06 Output Current 1 during Speed Search – 0.7 0.7 0.7 0.7 0.7
b8-04 Energy Saving Coefficient Value – 27.13 21.76 23.84 20.26 17.06
C6-02 Carrier Frequency Selection – 7 7 7 7 7
E2-01 Motor Rated Current A 370 500 650 900 1200
E2-02 Motor Rated Slip Hz 1.3 1.25 1 0.9 0.7
E2-03 Motor No-Load Current A 96 130 130 180 240
E2-05 Motor Line to Line Resistance Ω 0.02 0.014 0.012 0.009 0.006
E2-06 Motor Leakage Inductance % 20 20 20 20 20
E2-10 Motor Iron Loss for Torque Compensation W 3700 4700 5560 7833 11123
E5-01 Motor Code Selection Hex. FFFF FFFF FFFF FFFF FFFF
L2-02 Momentary Power Loss Ride-Thru Time s 2 2 2 2 2
L2-03 Momentary Power Loss Minimum Baseblock Time s 2 2.1 2.3 3.1 4.6
L2-04 Momentary Power Loss Voltage Recovery Time s 1 1 1 3 4.5
L3-24 Motor Acceleration Time for Inertia Calculations s 0.91 1.392 1.667 2.222 3.333
L8-02 Overheat Alarm Level °C 140 140 140 140 140
L8-35 Installation Method Selection – 0 0 0 0 0
n1-03 Hunting Prevention Time Constant ms 100 100 100 100 100