Installation
Instruction handbook b maXX 5000
Document No.: 5.09021.16
129
of 328
7
7.6 PE connection and RCD compatibility
Depending on the functional principle, leakage current >3.5 mA
AC
or >10 mA
DC
can flow
through the protective ground conductor. Consequently, a stationary ground conductor
connection in accordance with EN 61800-5-1 is required.
DANGER!
Risk of fatal injury from elec
trical current!
This product can cause direct and/or alternating
current in the protective ground con-
ductor.
The leakage current, due to the functional principle
of the device, can lead to prema-
ture triggering of the fault current protective device or generally prevent triggering of
it.
Therefore:
m Wher
ever a differential current device (RCD) is used for protection in case of direct
or indirect contact, only an RCD of the type B is permitted on the power supply side
of the device.
m Otherwise a different protec
tive measure must be utilized, such as separation from
the surrounding by means of double or enhanced isolation, or separation from the
power supply system by means of an isolating transformer, for example.

Table of Contents

Other manuals for Baumuller b maXX 5000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Baumuller b maXX 5000 and is the answer not in the manual?

Baumuller b maXX 5000 Specifications

General IconGeneral
BrandBaumuller
Modelb maXX 5000
CategoryServo Drives
LanguageEnglish

Related product manuals