UL notes
Instruction handbook bmaXX 5000
Document No.: 5.09021.19 Baumüller Nürnberg GmbH
94
of 346
4.3
4.3 UL notes
The notes below must be observed in case you consider UL 508 C.
ZRequired environmental conditions– on page 49
ZDesign– on page 87
ZInstallation procedure– on page 148
ZElectrical connections– as from page 164
Connections of ZPage 174– to ZPage 175–
ZRequirements for the connection cables– on page 134
ZRequirements for the motor temperature sensors– on page 147
n Note the maximum surrounding air temperature.
n Use in a pollution degree 2 environment only.
n Axis units (BM5X23, BM5X26, BM5X27, BM5X28, BM5X31, BM5X32, BM5X33, BM5X34,
BM5X35)are allowed to be used only in combination with mains rectifiers
(BM5031, BM5032, BM5043, BM5044, BM5174).
n Internal overload protection operates after exceeding 200 % of the motor full
load.
n Position of wiring terminals to indicate the proper connections for the power
supply, load, control circuit, and similar devices refer to ZPage 164–.
n Note tightening torque values marked for field terminals.
n Use 60°/75°copper wires only.
n Drives do not provide motor overtemperature sensing.