Technical data
Instruction handbook bmaXX 5000
Document No.: 5.09021.19
63
of 346
3
m BM504X mains rectifier unit without safety function
Footnotes refer to Zpage 68–.
BM5043 BM5043-A BM5043 BM5043-A
-XT0X-.. /-XI0X-.. / -XG0X-..
without charge resistor
-XR0X-.. /-XS0X-.. / -XW0X-..
with charge resistor
Input rated power
1)
45 kVA 61 kVA
14)
Input rated current (I
eff
)
1) 2) 3)
65 A 88 A
Distortion factor of the input current (THD
I
)
1)
57 % ± 10 % 180 % ± 10 %
Input peak current (I
eff
)
1) 2) 3)
98 A for max. 150 s 132 A for max. 150 s
DC link voltage
power supply dependent/rated
540 V
DC
at U
power supply
= 3 x 400 V
DC link capacitance (internal) 1000 µF
DC link discharge time
(internal DC link capacitance)
9)
Approx. 350 s
Total max. connectable capacitance
in the DC link (internal + external)
20 mF
Connection power at DC link
1) 5)
36 kW
Peak power at DC link
4) 6)
54 kW for max. 150 s
Capacitance DC link to PE 150 nF
Ready-to-operate after 7s
Max. charge-up time 10 s
Quick discharge
10)
5s
External brake resistor R
B
R
B
10.5
External brake resistor continuous power 58 kW
Quick discharge resistor -
Power loss with regard to power supply
7)
190 W
Power loss with regard to control
voltage supply
8)
Max. 25 W
Cooling air requirement power heat sink 100 m
3
/h - 100 m
3
/h -
Cooling air velocity power heat sink - > 5 m/s - > 5 m/s
Cooling air requirement
internal space of device
8m
3
/h