360/641 Bosch Rexroth AG | Tightening Technology 3 608 878 300
System 350 | 3 608 878 300/2019-03
MID 0038 Select job number
MID 0038 revision 001
Number of tightening
programs/tightening
applications
Number of tightening programs or tightening applications defined in the
job.
The value consists of two ASCII characters.
ID 12
2
Value range 0–99
Presetting -
Example:
Number 3
Value 03
2
List of tightening programs /
tightening applications
List of tightening programs with respective parameters. Field separator ":",
parameter end ";"
ChannelID: ProgNr/AnwNr:AutoValue:BatchSize;
ChannelID:"01" two ASCII characters
ProgNo/AppNo:"XXX" three ASCII characters
AutoValue:"0" one ASCII character
OKBatchSize:"YY" two ASCII characters
The value consists of one ASCII characters.
ID 13
2
Value range -
Presetting -
Example:
List aa:bbb:c:dd;aa:bbb:c:dd;
Value 01:005:0:03;
12
Data length revision 001
71+x
Table 6–88: MID 0033 revision 001
Parameter Comments Bytes
Sent by: superordinate computer
This command can be used to select the job number of the tightening channel.
Note: In the PLC assignment table, the Job <n> signal must be applied to the OP module or forwarded to the IL.
Revision: 001 (supported by Rexroth OP)
Data field: 3 bytes
Possible response: MID Error no. Comment
Command accepted 0005 -
Command error 0004 98 Request timeout in the control or PLC signal not
assigned in the PLC assignment table.
Table 6–89: MID 0038 revision 001
Parameter Comments Bytes
Job number Job number 0-99
The value consists of two ASCII characters.
ID -
Value range 00 99
Presetting -
Example:
Job number 01
Value 01
2
Data length revision 001
2