3 608 878 300 Tightening Technology | Bosch Rexroth AG 417/641
System 350 | 3 608 878 300/2019-03
MID 0501 Upload Output signal change
MID 0501 revision 001
Sent by: Tightening controller
The assignment of the output signals at the OP PLC module has changed.
Note: -
Revision: Number Supported by
001 Rexroth OP and Rexroth OP-Ford) and Rexroth OP-BMW
002 Rexroth OP and Rexroth OP-Ford) and Rexroth OP-BMW
Data field: Number of signals, 8 bytes or 16 bytes
Possible response MID Error no. Comment
Acknowledgement Upload output signal
change
0502 –
Table 6–114: MID 0501 revision 001
Parameter Comments Bytes
This revision outputs the values of the first eight (8) assignable output signals of the OP PLC module. The output is
effected in the order in which the signals have been stored by the user. The signals can be applied to the OP PLC
module from 1.0–1.7.
Signals ID none
Value range 0 (not active) or 1 (active)
Presetting -
Example:
Signals The signals can be assigned as desired.
Value 00100100, with:
–InCy=0
–Nok=0
–Ok=1
– AppOut3 = 0
– AppOut4 = 0
– AppOut6 = 0
– AppOut7 = 0
–CyCmp=1
8
Data length revision 001
8