5.2 Function Codes Table
5-6
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Auto torque boost/
Auto energy-saving operation
1
1: Constant torque load
2: Auto torque boost
3: Auto energy-saving operation (variable torque load)
4: Auto energy-saving operation (constant torque load)
5: Auto energy-saving operation with auto torque boost
Stop frequency
(Detection mode) *5
0: Actual speed / estimated speed
1: Reference speed
Stop frequency (Holding time)
Torque limiter 1 (Driving)
Drive control selection 1
0: V/f control without slip compensation
1: Vector control without speed sensor (dynamic torque
vector)
2: V/f control with slip compensation
3: V/f control with speed sensor *5
4: V/f control with speed sensor and auto torque boost *5
6: Vector control for induction motor with speed sensor *5
15: Vector control for synchronous motor without speed
sensor nor pole position sensor *5
0: Disable (No current limiter works.)
1: Enable at constant speed (Disable during ACC/DEC)
2: Enable during ACC/constant speed operation
20 to 200% (Rated current of the inverter for 100%)
Electronic thermal overload
protection for braking resistor
(Braking resistance value)
0.00: Resistance not required (Compatible mode with
FRENIC-Multi series) 0.01 to 999 Ω
Switching between ND, HD,
1: HND mode
3: HD mode
4: ND mode
ND/HD mode is not supported for 200V class series.
Factory default
A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
*5: Available at ROM version 0300 or later.