5.2 Function Codes Table
5-8
Code
Name Data setting range
Change when running
Data copying
Factory
Default
71 (1071): Hold line speed control frequency in the memory
*5 “LSC-HLD”
72 (1072): Count the run time of commercial power-driven
motor 1 *5 “CRUN-M1”
73 (1073): Count the run time of commercial power-driven
motor 2 *5 “CRUN-M2”
76 (1076): Select droop control “DROOP”
78 (1078): Select speed control parameter 1 *5 “MPRM1”
79 (1079): Select speed control parameter 2 *5 “MPRM2”
80 (1080): Cancel customizable logic “CLC”
81 (1081): Clear all customizable logic timers “CLTC”
82 (1082): Cancel anti-regenerative control “AR-CCL”
100: No function assigned “NONE”
171 (1171): PID control multistage command 1 “PID-SS1”
172 (1172): PID control multistage command 2 “PID-SS2”
* Inside the ( ) is the negative logic signal (OFF at
short-circuit)
* 0.00 is for acceleration and deceleration time cancel
(when performing soft-start and stop externally)
Torque limiter 2 (Driving)
0 (1000): Inverter running “RUN”
1 (1001): Frequency (speed) arrival “FAR”
Terminal [30A/B/C] function
2 (1002): Frequency (speed) detected “FDT”
3 (1003): Under voltage detected (inverter stopped) “LU”
4 (1004): Detected torque polarity “B/D”
5 (1005): Inverter output limiting “IOL”
6 (1006): Auto-restarting after momentary power failure
“IPF”
7 (1007): Motor overload early warning “OL”
8 (1008): Keypad operation enabled “KP”
10 (1010): Inverter ready to run “RDY”
15 (1015): Switch MC on the input power lines “AX”
16 (1016): Pattern operation stage transition “TU”
17 (1017): Pattern operation cycle completed “TO”
18 (1018): Pattern operation stage 1 “STG1”
19 (1019): Pattern operation stage 2 “STG2”
20 (1020): Pattern operation stage 4 “STG4”
21 (1021): Frequency (speed) arrival 2 “FAR2”
22 (1022): Inverter output limiting with delay “IOL2”
25 (1025): Cooling fan in operation “FAN”
26 (1026): Auto-resetting “TRY”
27 (1027): Universal DO “U-DO”
28 (1028): Heat sink overheat early warning “OH”
29 (1029): Synchronization completed *5 “SY”
30 (1030): Lifetime alarm “LIFE”
31 (1031): Frequency (speed) detected 2 “FDT2”
33 (1033): Reference loss detected “REF OFF”
35 (1035): Inverter outputting “RUN 2”
36 (1036): Overload prevention controlling “OLP”
37 (1037): Current detected “ID”
38 (1038): Current detected 2 “ID2”
39 (1039): Current detected 3 “ID3”
*5: Available at ROM version 0300 or later.
*10: 6.00s for inverters of nominal applied motor 22kW or below; 20.0s for those of 30kW or above.