5.2 Function Codes Table
5-9
FUNCTION CODES
Chap 5
Code
Name Data setting range
Change when running
Data copying
Factory
Default
41 (1041): Low current detected “IDL”
42 (1042): PID alarm “PID-ALM”
43 (1043): Under PID control “PID-CTL”
44 (1044): Under sleep mode of PID control “PID-STP”
45 (1045): Low torque detected “U-TL”
46 (1046): Torque detected 1 “TD1”
47 (1047): Torque detected 2 “TD2”
48 (1048): Motor 1 selected “SWM1”
49 (1049): Motor 2 selected “SWM2”
52 (1052): Running forward “FRUN”
53 (1053): Running reverse “RRUN”
54 (1054): Under remote mode “RMT”
56 (1056): Motor overheat detected by thermistor “THM”
57 (1057): Brake control “BRKS”
58 (1058): Frequency (speed) detected 3 “FDT3”
59 (1059): Terminal [C1] (C1 function) wire break detected
“C1OFF”
70 (1070): Speed valid *5 “DNZS”
71 (1071): Speed agreement *5 “DSAG”
72 (1072): Frequency (speed) arrival 3 “FAR3”
76 (1076): PG error detected *5 “PG-ERR”
77 (1077): Low DC link bus voltage detection “U-EDC”
79 (1079): During decelerating at momentary power failure
“IPF2”
80 (1080): Stop position override alarm *5 “OT”
81 (1081): Under positioning *5 “TO”
82 (1082): Positioning completed *5 “PSET”
83 (1083): Current position count over-flowed *5 “POF”
84 (1084): Maintenance timer counted up “MNT”
87 (1087): Frequency arrival and detected “FARFDT”
90 (1090): Alarm content 1 “AL1”
91 (1091): Alarm content 2 “AL2”
92 (1092): Alarm content 4 “AL4”
93 (1093): Alarm content 8 “AL8”
98 (1098): Light alarm “L-ALM”
99 (1099): Alarm output “ALM”
101 (1101): EN circuit failure detected “DECF”
102 (1102): EN terminal input OFF “ENOFF”
105 (1105): Braking transistor broken “DBAL”
111 (1111): Customizable logic output signal 1 “CLO1”
112 (1112): Customizable logic output signal 2 “CLO2”
113 (1113): Customizable logic output signal 3 “CLO3”
114 (1114): Customizable logic output signal 4 “CLO4”
115 (1115): Customizable logic output signal 5 “CLO5”
116 (1116): Customizable logic output signal 6 “CLO6”
117 (1117): Customizable logic output signal 7 “CLO7”
118 (1118): Customizable logic output signal 8 “CLO8”
119 (1119): Customizable logic output signal 9 “CLO9”
120 (1120): Customizable logic output signal 10 “CLO10”
* Inside the ( ) is written the negative logic signal setting
(OFF at short-circuit)
Frequency arrival delay timer
(FAR2)
Frequency arrival detection
width (Detection width)
*5: Available at ROM version 0300 or later.