5.2 Function Codes Table
5-10
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
E31
Frequency detection 1 (Level)
0.0 to 500.0 Hz
Y
Y
200V class
AJKU:60.0
400V class
ACE:50.0
JKU:60.0
Y
Y
Y
N
Y
5-128
E32
(Hysteresis width)
0.0 to 500.0 Hz
Y
Y
1.0
Y
Y
Y
N
Y
E34
Overload early
warning/Current detection
(Level)
0.00 (Disable), 1 to 200% of inverter rated current
(Inverter rated current dependent on F80)
Y
Y1
Y2
*3
Y
Y
Y
Y
Y
5-129
E35
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
Y
E36
Frequency detection 2
(Level)
0.0 to 500.0 Hz
Y
Y
200V class
AJKU:60.0
400V class
ACE:50.0
JKU:60.0
Y
Y
Y
Y
Y
5-130
E37
Current detection 2/
Low current detection
(Level)
0.00 (Disable), 1 to 200% of inverter rated current
(Inverter rated current dependent on F80)
Y
Y1
Y2
*3
Y
Y
Y
Y
Y
5-130
E38
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
Y
E39
Display coefficient for
transport time
0.000 to 9.999
Y
Y
0.000
Y
Y
Y
N
Y
5-130
E42
LED display filter
0.0 to 5.0 s
Y
Y
0.5
Y
Y
Y
Y
Y
5-130
E43
LED monitor (Item selection)
0: Speed monitor (Selectable with E48)
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID process command
12: PID feedback value
13: Timer value(for timed operation)
14: PID output
15: Load factor
16: Motor output
17: Analog signal input monitor
21: Current position pulse *5
22: Position error pulse *5
23: Torque current (%) *5
24: Magnetic flux command(%) *5
25: Input watt-hour
Y
Y
0
Y
Y
Y
Y
Y
5-131
E44
(Display when stopped)
0: Specified value
1: Output value
Y
Y
0
Y
Y
Y
Y
Y
5-132
E48
LED monitor
(Speed monitor item)
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Reference frequency
3: Motor rotation speed
4: Load rotation speed
5: Line speed
6: Transport time for specified length
7: Speed (%)
Y
Y
0
Y
Y
Y
Y
Y
5-132
E49
Torque Command Monitor *5
(Polarity selection)
0: Torque polarity
1: Plus for driving, Minus for braking
Y
Y
1
Y
Y
Y
Y
Y
5-132
E50
Display coefficient for speed
monitor
0.01 to 200.00
Y
Y
30.00
Y
Y
Y
Y
Y
5-133
E51
Display coefficient for “Input
watt-hour data
0.000 (Cancel/Reset). 0.001 to 9999
Y
Y
0.010
Y
Y
Y
Y
Y
5-133
E52
Keypad (Menu display mode)
0: Function code data setting mode (Menu 0, Menu1, and
Menu 7)
1: Function code data check mode (Menu 2 and Menu 7)
2: Full-menu mode
Y
Y
0
Y
Y
Y
Y
Y
5-134
E54
Frequency detection 3 (Level)
0.0 to 500.0Hz
Y
Y
200V class
J:50.0
AUK:60.0
400V class
ACEJ:50.0
UK:60.0
Y
Y
Y
Y
Y
5-134
E55
Current detection 3 (Level)
0.00 (Disable), 1 to 200% of inverter rated current
(Inverter rated current dependent on F80)
Y
Y1
Y2
*3
Y
Y
Y
Y
Y
5-134
E56
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
Y
Factory default

A (For Asia), C (for China), E (for Europe), U (For USA), J (for Japan), K (for Korea)
indicates quick setup target function code.
*3: The motor rated current is automatically set. Refer to 5.2.4 Motor constant(function code P03).
*5: Available at ROM version 0300 or later.

Table of Contents