5.2 Function Codes Table
5-11
FUNCTION CODES
Chap 5
Code
Name Data setting range
Change when running
Data copying
Factory
Default
Drive control
Related page
V/f
PG V/f
w/ PG
Torque control
PM
E59
Terminal [C1] function
selection
0: Current input (C1 function)
1: Voltage input (V2 function)
N
Y
0
Y
Y
Y
Y
Y
5-135
E61
Terminal [12] extended
function
0: None
1: Auxiliary frequency setting 1
2: Auxiliary frequency setting 2
3: PID process command
5: PID feedback value
6: Ratio setting
7: Analog torque limiter A
8: Analog torque limiter B
9: Torque bias *5
10: Torque command *5
11: Torque current command *5
17: Speed limit for forward rotation *5
18: Speed limit for reverse rotation *5
20: Analog signal input monitor
N
Y
0
Y
Y
Y
Y
Y
5-136
E62
Terminal [C1]
(C1 extended function)
N
Y
0
Y
Y
Y
Y
Y
E63
Terminal [C1]
(V2 extended function)
N
Y
0
Y
Y
Y
Y
Y
E64
Saving of digital reference
frequency
0: Auto saving (main power is turned off)
1: Save by turning key ON
Y
Y
0
Y
Y
Y
Y
Y
5-136
E65
Reference loss detection
0: Stop deceleration
20 to 120%, 999: Cancel
Y
Y
999
Y
Y
Y
N
Y
5-137
E76
DC link bus low-voltage
detection level
200 to 400 V (200 V class)
400 to 800 V (400 V class)
Y
Y
235
470
Y
Y
Y
Y
Y
5-137
E78
Torque detection 1 (Level)
0 to 300%
Y
Y
100
Y
Y
Y
Y
Y
5-138
E79
(Timer)
0.01 to 600.00 s
Y
Y
10.00
Y
Y
Y
Y
Y
E80
Torque detection 2/
low torque detection (Level)
0 to 300%
Y
Y
20
Y
Y
Y
Y
Y
E81
(Timer)
0.01 to 600.00 s
Y
Y
20.00
Y
Y
Y
Y
Y
E98
Terminal [FWD] function
0 (1000): Select multistep frequency (0 to 1 steps) “SS1”
N
Y
98
Y
Y
Y
N
Y
5-138
E99
Terminal [REV] function
1 (1001): Select multistep frequency (0 to 3 steps) “SS2”
N
Y
99
Y
Y
Y
N
Y
2 (1002): Select multistep frequency (0 to 7 steps) “SS4”
Y
Y
Y
N
Y
3 (1003): Select multistep frequency (0 to 15 steps) “SS8”
Y
Y
Y
N
Y
4 (1004): Select ACC/DEC time (2 steps) “RT1”
Y
Y
Y
N
Y
5 (1005): Select ACC/DEC time (4 steps) “RT2”
Y
Y
Y
N
Y
6 (1006): Select 3-wire operation “HLD”
Y
Y
Y
N
Y
7 (1007): Coast to a stop command “BX
Y
Y
Y
Y
Y
8 (1008): Reset alarm (Abnormal) “RST”
Y
Y
Y
Y
Y
9 (1009): External alarm “THR”
(9 = Active OFF/1009 = Active ON)
Y
Y
Y
Y
Y
10 (1010): Ready for jogging “JOG”
Y
Y
Y
N
N
11 (1011): Select frequency setting 2/ frequency setting 1
“Hz2/ Hz1”
Y
Y
Y
N
Y
12 (1012): Select Motor 2 “M2”
Y
Y
Y
Y
Y
13: DC braking command “DCBRK”
Y
Y
Y
N
N
14 (1014): Select torque limit 2/ torque limit 1 “TL2/ TL1”
Y
Y
Y
Y
Y
15: Switch to commercial power (50 Hz) “SW50”
Y
Y
N
N
N
16: Switch to commercial power (60 Hz) “SW60”
Y
Y
N
N
N
17 (1017): UP command “UP”
Y
Y
Y
N
Y
18 (1018): DOWN command “DOWN”
Y
Y
Y
N
Y
19 (1019): Allow function code editing
(Data change enabled) “WE-KP”
Y
Y
Y
Y
Y
20 (1020): Cancel PID control “Hz/PID”
Y
Y
Y
N
Y
21 (1021): Switch normal/ inverse operation “IVS”
Y
Y
Y
N
Y
22 (1022): Interlock “IL”
Y
Y
Y
Y
Y
23 (1023): Cancel torque control *5 “Hz/TRQ”
N
N
N
Y
N
24 (1024): Select link operation (RS-485, BUS option) “LE”
Y
Y
Y
Y
Y
25 (1025): Universal DI “U-DI”
Y
Y
Y
Y
Y
26 (1026): Select auto search for idling motor speed at
starting “STM”
Y
Y
N
N
Y
30 (1030): Force to stop “STOP”
(30 = Active OFF/1030 = Active ON)
Y
Y
Y
Y
Y
32 (1032): Pre-excite *5 “EXITE”
N
N
Y
Y
N
*5: Available at ROM version 0300 or later.