SITE TEST PROCEDURE
F - 5
8. Jog EL briefly up and then down, checking to see that the
resulting motion corresponds to the respective switch
commands. _______(Check)
9. Jog POL briefly CW and then CCW, checking to see that
the resulting motion corresponds to the respective switch
commands. (N/A if "POL" is unavailable) _______(Check)
10. Jog 4th Axis briefly CW and then CCW, checking to see
that the resulting motion corresponds to the respective
switch commands. (N/A if "4th Axis" is unavailable) _______(Check)
11. Repeat steps 1-10 for any remaining PMCU connections.
Record the number of connections. ______ (Record)
1.4 Miscellaneous Error and Fault Messages
1. In the drive cabinet, set the DRIVE CIRCUIT BREAKER to
OFF. Verify that the 7200 ACU display shows NO POWER
AT DRIVE CABINET. _______(Check)
2. In the drive cabinet, set the DRIVE CIRCUIT BREAKER to ON. _______(Check)
3. Press the EMERGENCY STOP button on the side of the
drive cabinet. Verify that the 7200 ACU display shows
E STOP. _______(Check)
4. Verify that the customer interface FLT contacts open. _______(Check)
5. Set the EMERGENCY STOP button to the out position. _______(Check)
6. Verify that the inverters reset and that there are no fault
messages displayed. _______(Check)
7. Verify a closed circuit between the customer interface FLT
terminals. _______(Check)
8. Repeat steps 1-7 for any remaining E-Stop interlocks and
record info in the following table.