Table 87: Parts and Tools Required for Connecting an EX Series Switch to Earth
Ground (continued)
Additional
InformationScrewdriver
Screws and
Washers
Grounding Lug
Specifications
Grounding Cable
Requirements
Earthing
Terminal
LocationSwitch
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 182.
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 WG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4200
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 182.
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4300
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 182.
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4500
See “Special
Instructions
to Follow
Before
Connecting
Earth Ground
to a Switch”
on page 182.
Phillips (+)
number 2
Two 10-32 x .25 in.
screws with #10
split-lock washer—
not provided
Two #10 flat
washers—
not provided
Panduit
LCC10-14BWL or
equivalent—
not provided
14 AWG (2 mm²),
minimum 90°C
wire, or as
permitted by the
local code
Left side of
the chassis
EX4550
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
The grounding
cable must be the
same gage as the
power feed cables
and as permitted
by the local code.
Rear panel
of the
chassis (on
lower left
side)
EX6210
Phillips (+)
number 2
Two ¼-20 x 0.5 in.
screws with #¼”
split-washer
—provided
Two #¼” flat
washers—
provided
Panduit
LCD2-14A-Q or
equivalent
—provided
6 AWG (13.3
mm²), minimum
60°C wire, or as
permitted by the
local code
Left side of
the chassis
EX8208
181Copyright © 2017, Juniper Networks, Inc.
Chapter 12: Connecting the Switch to Power

Table of Contents

Other manuals for Juniper EX4300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper EX4300 and is the answer not in the manual?

Juniper EX4300 Specifications

General IconGeneral
ModelEX4300
Virtual ChassisYes, up to 10 members
Layer 3 RoutingYes
10GBASE SFP+ Ports4
Jumbo Frames9216 bytes
MAC Address Table Size32, 000
Operating SystemJunos OS
Uplink Ports4 x 10GBASE SFP+
Power SupplyAC or DC options
Operating Temperature0°C to 45°C (32°F to 113°F)
Input Voltage100-240V AC
Operating Relative Humidity5 to 90% RH, non-condensing
Management OptionsCLI, Web UI, Junos Space
RedundancyYes, power supply and fans
Storage Temperature-40°F to 158°F (-40°C to 70°C)
Ports24 or 48

Related product manuals