15 Parameter reference
15.2 Parameter list
1056
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01090
C01091
Parameter | Name:
C01090 | LS_ParReadWrite 1-6: Index
Data type: INTEGER_32
Index: 23485
d
= 5BBD
h
From version 06.00.00
Parameter to be read or written.
Format: <code number>,<subcode number>
For a setting of "0,000", inputs wParIndex and wParSubindex are effective for addressing purposes instead.
Setting range (min. value | unit | max. value)
0.000 16000.000
Subcodes Lenze setting Info
C01090/1 0.000 LS_ParReadWrite_1
: Index
C01090/2 0.000 LS_ParReadWrite_2
: Index
C01090/3 0.000 LS_ParReadWrite_3
: Index
C01090/4 0.000 LS_ParReadWrite_4
: Index
C01090/5 0.000 LS_ParReadWrite_5
: Index
C01090/6 0.000 LS_ParReadWrite_6
: Index
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000
Parameter | Name:
C01091 | LS_ParReadWrite 1-6: Cycle time
Data type: UNSIGNED_16
Index: 23484
d
= 5BBC
h
From version 04.00.00
Time interval for cyclic reading/writing
Selection list
0 0 (by Execute)
20 20 ms
50 50 ms
100 100 ms
200 200 ms
500 500 ms
1000 1 s
2000 2 s
5000 5 s
10000 10 s
Subcodes Lenze setting Info
C01091/1 0: 0 (by Execute) LS_ParReadWrite_1
: Cycle time
C01091/2 0: 0 (by Execute) LS_ParReadWrite_2
: Cycle time
C01091/3 0: 0 (by Execute) LS_ParReadWrite_3
: Cycle time
C01091/4 0: 0 (by Execute) LS_ParReadWrite_4
: Cycle time
C01091/5 0: 0 (by Execute) LS_ParReadWrite_5
: Cycle time
C01091/6 0: 0 (by Execute) LS_ParReadWrite_6
: Cycle time
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1