Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 1069
15 Parameter reference
15.2 Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01211
C01213
C01215
Parameter | Name:
C01211 | MCK: Speed
Data type: INTEGER_32
Index: 23364
d
= 5B44
h
Display of the current speed data
Display range (min. value | unit | max. value)
-214748.3647 units/s 214748.3647
Subcodes Info
C01211/1 MCK: Max. traversing speed 100%_C11
• Display of the maximum traversing speed based on
the reference speed set in C00011
.
C01211/2 MCK: Set speed
• From version 12.00.00
C01211/3 MCK: Actual speed
• From version 12.00.00
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10000
Parameter | Name:
C01213 | MCK: Max. traversing distance
Data type: INTEGER_32
Index: 23362
d
= 5B42
h
Display of current position limits
Display range (min. value | unit | max. value)
-2147480000 units 2147480000
Subcodes Info
C01213/1 MCK: Max. traversing distance
• Display of the maximum distance to be traversed
referred to the 32-bit display area (max. 2147483647
increments).
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01215 | MCK: Following error
Data type: INTEGER_32
Index: 23360
d
= 5B40
h
Limits for following error monitoring system
Following error monitoring system
Setting range (min. value | unit | max. value)
0.0000 units 214748.0000
Subcodes Lenze setting Info
C01215/1 0.0000 units MCK: Following error limit 1
• First limit of the maximum following error for
monitoring and response activation.
C01215/2 0.0000 units MCK: Following error limit 2
• Second limit of the maximum following error for
monitoring and response activation.
C01215/3 0.0000 units MCK: Following error SetPos=ActPos
• From version 14.00.00
Monitoring of the following error in case of controller
inhibit
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10000