Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23 1099
15 Parameter reference
15.2 Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01701
C01702
C01703
Parameter | Name:
C01701 | Energy saving mode: toff min
Data type: UNSIGNED_16
Index: 22874
d
= 595A
h
From version 17.00.00 onwards
Minimum time for which the inverter is to remain in the energy saving mode (TPm, Time Pause min).
Setting range (min. value | unit | max. value)
0 s 65535
Subcodes Lenze setting Info
C01701/1 0 s Energy saving mode 1: toff min
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01702 | Energy saving mode: toff
Data type: UNSIGNED_16
Index: 22873
d
= 5959
h
From version 17.00.00 onwards
Time required until entering the energy saving mode (TtP, Time to Pause)
If the "quick stop" energy saving function is to be used, this time must always be set to a greater value than the
maximum time required for braking via the quick stop function.
Setting range (min. value | unit | max. value)
0 s 65535
Subcodes Lenze setting Info
C01702/1 0 s Energy saving mode 1: toff
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C01703 | Energy saving mode: ton
Data type: UNSIGNED_16
Index: 22872
d
= 5958
h
From version 17.00.00 onwards
Time used for exiting the energy saving mode (TtO, Time to Operate).
Setting range (min. value | unit | max. value)
0 s 65535
Subcodes Lenze setting Info
C01703/1 0 s Energy saving mode 1: ton
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1