15 Parameter reference
15.2 Parameter list
1100
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01704
Parameter | Name:
C01704 | Energy saving mode: Function
Data type: UNSIGNED_16
Index: 22871
d
= 5957
h
From version 17.00.00 onwards
Response of the device in energy saving mode
Setting range (min. hex value | max. hex value)
0x0000 0xFFFF
Value is bit-coded: Info
Bit 0 CINH With entering the energy saving mode, controller inhibit
is set.
Controller inhibit is reset when the "Pause-End"
command is received.
Diagnostics of active controller inhibit with C00158/
0, bit 9
Display: "Energy saving mode"
Bit 1 QSP When the "Pause-Req" command is received, the inverter
executes a quick stop.
Quick stop is cancelled when the "Pause-End"
command has been received.
Quick stop diagnostics with C00159/0, bit 9
Display: "Energy saving mode"
Bit 2 Dimming the LEDs Most of the LEDs of the inverter are switched off or their
lightling intensity is reduced.
Only a few LEDs remain active in order to check the
vitality of the inverter, e.g. the "DRV-RDY" LED.
Bit 3 Reserved
Bit 4 Decoupling the IOs The digital output terminals are decoupled from the
application (FB Editor).
The output levels for these outputs can be defined via
the decoupling values.
In order to render the decoupling values effective,
decoupling must be activated via the following
parameters:
•Digital outputs: C00447/0
and C00448/0
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved
Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Off Deactivate energy saving mode.
Subcodes Lenze setting Info
C01704/1 0x0000 Energy saving mode: Comp. to be switched off
Read access Write access CINH PLC STOP No transfer COM MOT