Loading...
15 Parameter reference
15.2 Parameter list
1144
Lenze · 8400 HighLine · Reference manual · DMS 12.0 EN · 06/2017 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02840
C02841
C02842
Parameter | Name:
C02840 | CountInx: Parameter
Data type: UNSIGNED_32
Index: 21735
d
= 54E7
h
From version 02.00.00
Starting and comparison values for digital count inputs
Use DI1(6) as counting input
Setting range (min. value | unit | max. value)
0 Incr. 2147483647
Subcodes Lenze setting Info
C02840/1 0 incr. CountIn1: Starting value
C02840/2 65535 incr. CountIn1: Comparison value
C02840/3 0 incr. CountIn6: Starting value
C02840/4 65535 incr. CountIn6: Comparison value
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C02841 | CountInx: Counter content
Data type: UNSIGNED_32
Index: 21734
d
= 54E6
h
From version 02.00.00
Display of the current counter content of the digital count inputs
Use DI1(6) as counting input
Display range (min. value | unit | max. value)
0 Incr. 2147483647
Subcodes Info
C02841/1 CountIn1: Counter content
C02841/2 CountIn6: Counter content
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C02842 | FreqInxx: Offset
Data type: INTEGER_16
Index: 21733
d
= 54E5
h
From version 02.00.00
Offset for digital frequency inputs
Using DI1(6) and DI2(7) as frequency inputs
Setting range (min. value | unit | max. value)
-199.99 % 199.99
Subcodes Lenze setting Info
C02842/1 0.00 % FreqIn12: Offset
C02842/2 0.00 % FreqIn67: Offset
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100